Fire-Rated Glass: What to Specify for Fire Doors and Compartment Walls

Fire-rated glass is a mandatory requirement in fire doors, glazed partitions and compartment walls β€” but specifying the right product is more complex than simply ordering β€œfire glass”. The right choice depends on the fire rating required, the location, and whether you need integrity alone or integrity plus insulation.

2026-11-16β€’8 min read

Every glazed fire door, corridor partition and compartment wall that contains a vision panel or glazed section must use glass tested and certified to the correct fire resistance rating. Using the wrong glass β€” or specifying it incorrectly β€” creates a compliance gap that can result in failed inspections, costly remediation and, in the worst case, a product that does not perform in a fire.

This guide explains how fire resistance classifications work, what glass types are available, where each is used, and what trade buyers need to include on a compliant order. It is written for glaziers, builders, fit-out contractors and architects specifying fire-rated glazing for UK projects.

What does β€œfire-rated glass” actually mean?

Fire-rated glass is glass that has been independently tested and certified to resist the passage of fire and/or heat for a defined period. The certification is based on a furnace test in which the glass assembly β€” including the frame and fixings β€” is exposed to a standard fire curve and monitored for failure.

The key point is that the rating applies to the tested assembly, not to the glass in isolation. A pane of certified fire glass installed in an uncertified frame, or in a frame with the wrong fixings, does not constitute a compliant fire-rated installation. This is one of the most common specification errors on site.

The two key performance criteria: integrity and insulation

Fire resistance ratings are built from two distinct performance criteria, used individually or in combination:

  • Integrity (E): The glazing prevents the passage of flames and hot gases for the rated period. The pane remains in position and seals the opening. It does not, however, limit the radiation of heat through the glass to the unexposed face. A person standing 1 metre from the glass on the safe side may still be exposed to significant radiant heat even though flames cannot pass through.
  • Insulation (I): The glazing limits the temperature rise on the unexposed face to no more than 140 Β°C average or 180 Β°C at any point above the starting temperature. Insulating glass protects people from radiant heat injury and prevents secondary ignition of materials on the safe side.

A combined EI rating means the glass provides both integrity and insulation. An E-only rating means integrity only β€” the glass stops flames but transmits heat.

Why it matters in practice

An E-only rated vision panel in a fire door is acceptable where people will evacuate quickly and not stand close to the door for extended periods. An EI-rated panel is required where a compartment wall protects an escape route or where people may be trapped and need protection from radiant heat for the full duration of the fire rating.

Fire resistance classifications and time ratings

Fire resistance periods are expressed in minutes. The classification combines the performance criteria and the time rating. Common classifications used in UK construction include:

  • E30: Integrity only, 30 minutes β€” the minimum for most fire doors in residential buildings
  • E60: Integrity only, 60 minutes β€” required for fire doors protecting escape routes in higher-risk or taller buildings
  • EI30: Integrity and insulation, 30 minutes β€” common for glazed partitions protecting escape corridors
  • EI60: Integrity and insulation, 60 minutes β€” required for compartment walls in hospitals, schools, office buildings and multi-occupancy residential
  • EI90 / EI120: Higher ratings for stairwell enclosures, plant rooms, compartment walls in high-rise and high-risk buildings

The required classification for any given location is determined by the building's fire strategy, which is set by the architect or fire engineer based on building type, occupancy and Building Regulations Approved Document B. Never assume a rating β€” always confirm it against the fire strategy for the project.

Key standard

Fire resistance classification for glass in the UK follows BS EN 13501-2 (the classification standard for construction products exposed to fire). The test method for glazed elements is BS EN 1364-1 (non-load-bearing walls) and BS EN 1634-1 (fire resistance of door and shutter assemblies). Products must carry a Declaration of Performance (DoP) and CE or UKCA mark; a European Technical Assessment (ETA) or third-party test evidence is required for the assembly.

Common fire-rated glass types

Several distinct glass technologies are used for fire-rated glazing. Each has different performance characteristics, appearance and cost implications.

Georgian wired glass

Wired glass is the traditional fire glazing product β€” float glass with a welded wire mesh embedded during manufacture. The wire holds the glass in position when it cracks under heat, preventing the opening from becoming unprotected. Wired glass provides E-only integrity; it transmits heat freely and provides no insulation.

Wired glass has fallen significantly out of favour in new construction. Its safety glazing performance is poor β€” it breaks into large shards β€” and it cannot satisfy BS 6206 Class B or A fragmentation requirements in most impact locations. It has been largely replaced by ceramics and clear fire glass in new-build and refurbishment projects. It may still be found in older existing installations.

Borosilicate glass

Borosilicate glass (the glass used in laboratory and cookware applications) has a very low coefficient of thermal expansion, which means it resists thermal shock better than soda-lime float glass. It is used in some fire door vision panels as an E-rated product and is typically available in 6 mm thickness. It is clear and visually similar to ordinary float glass.

Borosilicate provides integrity only and is used primarily in fire door vision panels where an E30 rating is sufficient. It is not suitable for large panels or for applications requiring insulation.

Ceramic glass

Ceramic glass (also called pyroceramic or glass-ceramic) is manufactured by a controlled crystallisation process that converts amorphous glass into a polycrystalline material with near-zero thermal expansion. It can withstand direct flame contact and extreme temperature differentials without cracking.

Ceramic glass is widely specified for E30 and E60 fire door vision panels and glazed screens where integrity is required and the aesthetic of a clear, unobstructed view is important. Products such as Schott PYRAN and NSG Pyroswiss are common examples. Ceramic glass provides integrity (E) only β€” it does not insulate, and in a 60-minute fire it will transmit enough heat to cause radiant burn injury at close range.

Transparent fire-rated intumescent glass (EI-rated)

For applications requiring both integrity and insulation, the solution is a composite fire glass product β€” typically a laminated build-up containing one or more transparent intumescent gel layers between glass plies. Under normal conditions the glass appears clear. When exposed to fire, the gel layers expand and turn opaque white, absorbing heat and preventing its transmission to the unexposed face.

These products β€” such as Pilkington Pyrostop, Saint-Gobain Contraflam, and similar branded systems β€” are available in EI30, EI60, EI90 and EI120 classifications. They are significantly more expensive than ceramic or borosilicate glass and are typically supplied as proprietary systems that must be installed in certified frames from the same manufacturer.

The panel size, frame system, fixings and installation method are all part of the tested assembly. Substituting any element β€” using a different frame profile, a different fixing spacing, or a different intumescent seal β€” invalidates the certification and must be agreed in advance with the system supplier.

KH Glass tip

If you are tendering a project that includes fire-rated glazing, confirm the required classification (E or EI, and the time rating) with the fire engineer or architect before pricing the glass. The difference between an E60 ceramic panel and an EI60 intumescent panel can be a factor of five or more in cost per square metre, and the frame and installation requirements are completely different.

Where fire-rated glazing is required

Approved Document B (Fire Safety) in England and Wales sets out the locations where fire resistance is required. Common locations where fire-rated glass is specified include:

  • Fire doors β€” vision panels in FD30 and FD60 fire doors in residential, commercial and institutional buildings; vision panels must be glazed with a certified fire glass to maintain the door's fire resistance rating
  • Protected escape routes β€” glazed screens and partitions forming the walls of protected corridors, lobbies and stairwells in offices, schools, hospitals and multi-storey residential buildings
  • Compartment walls and floors β€” glazed sections in walls that divide a building into fire compartments; the glazing must achieve the same fire rating as the wall itself
  • Atria and large open-plan spaces β€” glazed screens used to separate atria from corridors or escape routes in commercial and mixed-use developments
  • Server rooms and high-risk areas β€” glazed partitions where fire compartmentation protects critical or high-value contents

What to include on a fire-rated glass order

A correctly briefed fire glass order must include more information than a standard cut-glass order. Errors at the ordering stage can result in a product that cannot be installed compliantly or that fails inspection. Include the following on every fire-rated glass enquiry:

  • Required classification: State the full classification β€” e.g. E30, EI60. Do not simply write "fire glass".
  • Application: Fire door vision panel, glazed partition, compartment wall, etc. β€” this affects the glass type and frame requirements.
  • Panel size: Width Γ— height in millimetres. Fire ratings are only valid up to the maximum panel size tested; exceeding tested limits requires a new assessment.
  • Frame system: The frame manufacturer and profile reference, particularly for EI-rated intumescent glass systems where the frame is part of the certified assembly.
  • Safety glazing requirement: State whether the panel is in a critical safety glazing location (Part N). Many fire glass products satisfy BS 6206 Class B or C, but confirm this with the supplier before ordering.
  • Documentation required: Confirm whether you need a Declaration of Performance, test evidence, CE/UKCA certificate or third-party certification. Many projects require a copy of the test certificate for the building control file.

Fire glass and safety glazing: a common confusion

Fire-rated glass and safety glazing (Approved Document N) are separate requirements that sometimes apply to the same location. A vision panel in a fire door may be in a critical location under Part N β€” for example, within 300 mm of the door edge up to 1,500 mm from the floor β€” in which case the glass must satisfy both the fire rating and the safety glazing fragmentation requirement simultaneously.

Ceramic glass and most EI intumescent glass products satisfy BS 6206 Class B or C requirements, but always confirm this with the specific product's test evidence. Wired glass does not satisfy Part N safety glazing requirements in most critical locations and should not be specified in new installations.

Summary: quick specification guide

Fire door vision panel (FD30): E30 β€” 6 mm borosilicate or ceramic glass in a certified frame

Fire door vision panel (FD60): E60 β€” ceramic glass (e.g. PYRAN Platinum) in a certified frame

Escape corridor partition (30-min): EI30 β€” intumescent gel laminate in a system-certified frame

Compartment wall glazing (60-min): EI60 β€” intumescent gel laminate in a system-certified frame; confirm max panel size against test evidence

High-rise/institutional compartment wall: EI90 or EI120 β€” specialist intumescent laminate; structural engineer and fire engineer sign-off required

KH Glass supplies fire-rated glass for trade customers across Birmingham, the Midlands and nationwide. Whether you are glazing fire door vision panels, corridor partitions or compartment walls, our team can advise on the right product for the classification you need and ensure your order arrives with the correct documentation. Send your enquiry to [email protected], or get in touch for a trade quote. For related compliance information, see our guide to safety glazing regulations under Part N.